The new Cibin monoblock range use the latest generation ultra-low GWP refrigerants. With a GWP of only 146, R455A is the definitive solution for future low medium temperature commercial and industrial refrigeration.
After multiple tests and studies based on the entire cold chain, it has been shown that the TEWI (Total equivalent warming impact) of machines operating with R455A is significantly lower thanks both to the refrigerant, COP and the ease of managing the machines, which are more user-friendly compared to old R404A machines.

The refrigerant used is composed of a mildly flammable azeotropic mixture (A2L in accordance with ISO 817). However, the use of R455A is made safe (in compliance with the principal safety standards) due to the specific flammability properties of the refrigerant, which include:
a) Relatively high lower flammability limit equal to 11,8% (LFL);
b) Relatively low upper flammability limit compared to the low flammability limit 12,9% (UFL);
c) Minimum ignition energy more than 1000 times higher than propane;
d) Flame propagation speed lower than 1,5cm/s.

Sealed circuit
• Hermetic compressor
• Electronic fans
• Anti-vibration compressor brackets
• Air condensation
• Galvanized powder coated sheet steel body
• Evaporator body of aluminium-magnesium alloy
• Evaporator of copper pipes and aluminium fins
• Condenser of copper pipes and aluminium fins
• Automatic restarting low pressure switch (to be welded)
• Automatic restarting high pressure switch
• Compressor timer management to avoid too near start-ups
• Axial fan
• Condensation control device *
• Thermic compressor protection
• General magnete-thermal protection
• Thermostatic expansion valve with external equalization *
• Suction pressure relief valve (only for low temperature models)
• Dehydrator filter
• Suction-side liquid separator *
• Defrost hot gas solenoid valve
• Automatic hot gas defrosting
• Condensation outlet siphon
• Condensation outlet resistor (only for low temperature models)
• Cold room ceiling light and power source cable with related protection
via fuse
• Ambient temperature probe
• Defrosting end temperature probe
• Condensation control temperature probe*
• Connecting cable for door resistor with protection 4A fuse
(only for low temperatures models) and related protection with fuses
• Connecting cable for door micro switch to turn off the system and to turn
on the light at door opening
• Transformer
• Digital display with temperature indicator at one decimal
• On/Off switch
• Cold room light switch
• Running state display: cold – defrosting – evaporator fans – alarm status
• Programming keys
• Alarm display
• Manual defrosting key
• Acoustic alarm
• High temperature alarm
• Low temperature alarm
• High temperature alarm dirty condenser
• Low temperature alarm condenser
• Open door alarm
• High pressure alarm
• Defrosting end alarm because of time-out
• Alarm ambient temperature probe defect
• Alarm defrosting end temperature probe defect
• Alarm condensation control temperature probe defect
• Timer emergency running in case of these events:
– Ambient temperature probe defect
– Defrosting end temperature probe defect
– Condensation control temperature probe defect
– Cold room door open (if there is door micro switch)
• Pre-set connection for Frigotel® supervision

  • • Micro porta
    • Condensazione ad acqua con ricevitore di liquido, valvola regolatrice pressostatica, attacchi da ½”
    •Tensione alimentazione speciali
    • Versione tropicalizzata
    • Regolatore di velocità ventole condensatore
    • Monitor di tensione per fermata macchina in caso di alimentazione non corretta
    • Modulo elettronico per il collegamento al sistema di supervisione Frigotel®
    • Evaporatore con verniciatura in cataforesi
    • Condensatore con verniciatura in cataforesi

* dipende dal modello

ssssssssssssssssssssssssss
Cibin’s refrigerating equipment is classed as food and agricultural machinery (MACHINES DIRECTIVE 2006/42/EC), destined for the treatment
of food products.
The machine is designed for the conservation of foods and/or “fresh” products at temperatures indicated in annexes.
It has been designed to work in ambient temperatures from +16°C to +43°C (class T).
It has been designed to maintain a set temperature in a refrigerated cold room suitable for such uses.
The machine is not designed for use in cold rooms situated outside.
The machine is not designed for installation and use in an environment where there is risk of explosion.
Any use other than that permitted shall be considered improper, and in this case the Manufacturer will decline all liability.
The machine is not designed for the conservation of products, which produce corrosive substances.

NORCA R455A N 50Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125N 230/1+N/50 1137 9,0 7,5
NORCA 07125N 230/1+N/50 1323 12,0 10,0
NORCA 09125N 230/1+N/50 1562 13,0 11,0
NORCA 18225N 230/1+N/50 1701 18,5 15,5
NORCA 21225N 230/1+N/50 2089 21,0 17,0
NORCA 24225N 230/1+N/50 2635 26,5 21,0
NORCA 37325N 230/1+N/50 3663 39,5 31,5
NORCA 37325N 400/3/50 3716 41,0 32,5
NORCA 42325N 230/1+N/50 3962 44,0 35,0
NORCA 42325N 400/3/50 3625 42,5 34,0
NORCA 67235N 230/1+N/50 4405 66,0 52,0

CAPACITY
Te= -10°C ; Tcond= + 40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature = 0 °C
Ambient Temperature = 32°C

NORCA R455A B 50Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125B 230/1/50 761 6,0
NORCA 08125B 230/1/50 1298 9,0
NORCA 17225B 230/1/50 1442 15,0
NORCA 17225B 400/3/50 1458 15,0
NORCA 23225B 230/1/50 2151 24,0
NORCA 23225B 400/3/50 2101 23,0
NORCA 32325B 400/3/50 2203 34,5
NORCA 43325 BS 400/3/50 3327 44,0
NORCA 82235 BS 400/3/50 4711 83,5

CAPACITY
Te=-30°C;Tcond=+40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature= -20 °C
Ambient Temperature= 32°C

NORCA R455A N 60Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125 N 230/1/60 1098 7,2 8,3
NORCA 07125 N 230/1/60 1412 10,0 11,7
NORCA 09125 N 230/1/60 1730 11,3 13,2
NORCA 21225 N 230/1/60 2407 16,8 19,9
NORCA 24225 N 230/1/60 3011 18,1 21,5
NORCA 37325 N 400/3/60 3682 23,0 27,5
NORCA 42325 N 400/3/60 4102 31,2 37,5
NORCA 67225N 400/3/60 4862 54,8 66,8

CAPACITY
Te= -10°C ; Tcond= + 40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature = 0 °C
Ambient Temperature = 32°C

NORCA R455A B 60Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125 B 230/1/60 863 6,5
NORCA 08125 B 230/1/60 1209 8,5
NORCA 17225 B 400/3/60 1689 16,1
NORCA 23225 B 400/3/60 2520 25,7
NORCA 32325 B 400/3/60 2568 36,1

CAPACITY
Te=-30°C;Tcond=+40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature= -20 °C
Ambient Temperature= 32°C

NORCA R455A N Water Condensation 50Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125N-W 230/1+N/50 1137 10,0 8,5
NORCA 07125N-W 230/1+N/50 1323 13,0 11,0
NORCA 09125N-W 230/1+N/50 1562 15,0 12,0
NORCA 18225N-W 230/1+N/50 1701 20,0 16,0
NORCA 21225N-W 230/1+N/50 2089 23,5 19,0
NORCA 24225N-W 230/1+N/50 2635 29,5 23,5
NORCA 37325N-W 230/1+N/50 3663 44,0 35,0
NORCA 37325N-W 400/3+N/50 3716 44,0 35,0
NORCA 42325N-W 230/1+N/50 3962 49,0 39,0
NORCA 42325N-W 400/3+N/50 3625 46,5 36,5
NORCA 67235N-W 400/3+N/50 4405 69,5 54,5

CAPACITY
Te=-10°C;Tcond=+40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature = 0 °C
Ambient Temperature = 32°C

NORCA R455A B Water Condensation 50Hz

Model Power supply Capacity
Watt
Volume A
Volume B
Technical Sheet
(Register for download)
NORCA 06125B-W 230/1+N/50 761 7,0
NORCA 08125B-W 230/1+N/50 1298 10,0
NORCA 17225B-W 230/1+N/50 1442 17,0
NORCA 17225B-W 400/3+N/50 1458 17,0
NORCA 23225B-W 230/1+N/50 2151 27,0
NORCA 23225B-W 400/3+N/50 2101 26,5
NORCA 32325B-W 400/3+N/50 2203 37,5
NORCA 43325BS-W 400/3/50 3327 49,0
NORCA 82235BS-W 400/3/50 4711 90,5

CAPACITY
Te=-30°C;Tcond=+40°C

VOLUME
Vol. A = Cell insulation: All surfaces
Vol. B = Cell insulation: All walls except floor (volume calculation conditions)
Cell Temperature = -20 °C
Ambient Temperature = 32°C